Características
| Parámetro | Especificación |
| Specification | |
| Cells Per Unit | 6 |
| Voltage Per Unit | 12 |
| Nominal Capacity | 18Ah@20hour-rate to 1.75V per cell @25°C |
| Weight | Approx. 5.2 Kg (Tolerance ±3.0%) |
| Internal Resistance | Approx. 14 mΩ |
| Terminal | F3(M5)/F13(M5) |
| Max. Discharge Current | 180A (5 sec) |
| Short Circuit Current | 750A |
| Design Life | 6~8 years (Float charging) |
| Recommended Maximum Charging Current | 5.4 A |
| Reference Capacity |
C3: 14.0AH C5: 15.8AH C10: 16.9AH C20: 18.1AH |
| Standby Use Voltage |
13.7 V~13.9 V @ 25°C Temperature Compensation: -3mV/°C/Cell |
| Cycle Use Voltage |
14.6 V~14.8 V @ 25°C Temperature Compensation: -4mV/°C/Cell |
| Operating Temperature Range |
Discharge: -20°C~60°C Charge: 0°C~50°C Storage: -20°C~60°C |
| Normal Operating Temperature Range | 25°C ± 5°C |
| Self Discharge | RITAR Valve Regulated Lead Acid (VRLA) batteries can be stored for up to 6 months at 25°C and then recharging is recommended. Monthly Self-discharge ratio is less than 3% at 25°C. Please charge batteries before using. |
| Container Material | A.B.S. UL94-HB, UL94-V0 Optional. |